Description
Danfos KPI35 Pressure Switch INSTALLATION & USE The Danfos KPI pressure switches are used for water pump control and dry run protection in monitoring and alarm systems in a wide variety of industry applications. The KPI pressure switches are suitable for liquid and gaseous fluid. Adjustment Range 0.2 – 8 Bar FEATURES Wide setting range Shock and impact resistant Snap action electrical contacts minimize chatter, bounce, and wear, and ensure long term electrical and mechanical reliability Small dimensions. Space saving – easy to install in panels Electrical connection from front of the unit makes rack mounting easier and also saves space Suitable for alternating current and direct current Single pressure switches and thermostats are fitted with a single pole double throw contact system (SPDT), Can be used for both liquids and gases (KPI) Manual trip function enables electrical connections verification without any tools or pressure changes in the application TECHNICAL DETAILS: Adjustment Range: 0.2 – 8 Bar Differential: ( min) 0.5 bar – (max) 2 bar Fluid: Gaseous media and liquids Ambient temperature -40 – 65 °C (for max. 2 hours up to 80 °C) Media temperature -40 – 100 °C Connection: G 1/4 A Max working pressure: 18 bar